Support for Model: 25PTOC-17/A

25kw PTO Generator

General Information
Parts List
Categories: ,

Share your thoughts!

Let us know what you think...

What others are saying

  1. Question

    Terry Winstead

    I have a 25 kw Winco pto generator. Do you sell a line conditioner/ voltage regulator device to limit output to 230 v even if tractor rpm increases resulting in 250v output from the generator.

    Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

    Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

    • Dale Riebel

      Dale Riebel

      Terry, Winco does sell automatic voltage regulators, however I would not recommend installing one on your product. No load voltage should be set around 250 volts. Ideally at 1/2 load you would operate at 240 volts. Full load at approximately 230 volts. Your model is regulated by the input speed from the tractor, and the governor on the tractor should compensate for any load applied to the generator.

      Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal

      Something wrong with this post? Thanks for letting us know. If you can point us in the right direction...

×

Login

Continue as a Guest