What is the difference between a solid and a switched neutral?

While searching for the right transfer switch, you will want to know how your application requires the neutral to be handled. The rules vary by application and in some cases depend upon the authority having jurisdiction (Local electrical inspector).

solid neutral
Solid Neutral

Solid Neutral

A solid neutral switch provides basic load switching. The neutral of the generator, utility and building are permanently connected inside the transfer switch. The transfer only switches the hot (power) leads. In this application you need one pole on the switch for each hot lead.

Switched Neutral

Switched Neutral
Switched Neutral

A switched neutral transfer switch only allows the utility or generator neutral to be connected to the building load at a time. Since the neutral is switching between sources another pole on the transfer switch is required.

What is the difference between service and non-service entrance rated transfer switches?

The National Electric Code (NEC) requires a way for disconnecting the electrical service where it enters a building. This main circuit breaker prevents the building from demanding too much current from the utility creating a dangerous conditions. This circuit breaker may be in a separate panel or part of a service entrance rated transfer switch.

CB Service Disconnect
CB Service Disconnect
Click to enlarge

Non-Service Entrance Rated

There isn’t any over-current protection within a non-service entrance rated transfer switch. Therefore, when you install this type of transfer switch, it will be after the service disconnect panel.

If you find a non-fusible manual transfer switch, it does not have over-current protection. Non-fusible switches are not service entrance rated and cannot have the over-current protection added.

SE Rated
SE Rated Switch
Click to enlarge

Service Entrance Rated

Service entrance switches will have a service disconnect at the utility side. This installation requires less components, making it ideal for new construction, which can be more cost effective.

At WINCO, we offer ASCO service entrance rated switches equipped with an additional disconnect breaker.

Can I use my GFCI protected generator with a transfer switch?

First, lets discuss what GFCI protected means. GFCI stands for ground-fault circuit interrupter. You will recognize the outlets in your home, they are the ones with test and reset buttons. This is to eliminate the risk of an electric shock. On many of our generators, GFCI protection is part of the main line circuit breaker.

You can use a transfer switch with a full panel GFCI protected generator. When looking at transfer switches, you will need one with a switched neutral.

3-POLE SWITCHED NEUTRAL

A 3-pole transfer switch with a switched neutral is single phase. The switching mechanism will break the two hot legs of the circuit, in either direction, before the neutral is broken. It will then close the neutral before the two hot legs close, preventing the generator’s circuit breakers from nuisance tripping and protects inductive motors and sensitive loads.

This style of switched neutral transfer switch is also recommended for safe use with any generator that has a bonded neutral.

What is the difference between an ASCO secure and non-secure enclosure?

When you think of an item being “secure”, like us, you probably think that something is lockable. In most circumstances, you are right. However, when ASCO says their switch has a secure enclosure, they are saying that the enclosure has extra protection from UV rays. All ASCO transfer switches require a key, tool or both to gain access to live parts. Not all ASCO transfer switches are protected from potential harmful effects of UV radiation.

Non-Secure

These enclosures have a single door access to the inside equipment. Controls and displays are mounted in the door, thus they are exposed to direct sunlight and other environmental conditions.

If you are installing the transfer switch in an area where UV protection isn’t a main concern, the non-secure enclosure would be a great choice.

Secure

secured

Secure enclosures have a door-over-door construction, therefore, protecting the controls and displays from sunlight with some extra protection from precipitation.

UV Exposure
Solar Radiation Exposure Map

High UV radiation levels, extreme temperatures, and conditions such as elevated humidity, high altitude, and air pollution, may increase the rate of degradation of display and control materials.

What is a NEMA enclosure on a transfer switch?

A transfer switch can be damaged or create dangerous conditions if it is exposed to dirt or water. Therefore, it is essential that the transfer switch has an enclosure designed for the location and the risks it will be exposed to.

NEMA stands for National Electrical Manufacturers Association. NEMA represents nearly 325 electrical equipment and medical imaging manufacturers who make safe, reliable, and efficient products and systems.

For those who like the full technical definition keep reading. We included some pictures for the visual learners.

NEMA 1

For indoor use only.

The NEMA 1 enclosure protects personnel from gaining easy access to hazardous parts. Also, it will protect the equipment inside the enclosure of falling dirt.

NEMA 3R

NEMA 3R

For indoor or outdoor use.

The NEMA 3R enclosure protects personnel from gaining easy access to hazardous parts. Also, it will protect the equipment inside the enclosure of falling dirt, and the formation of ice. It also has an ingress protection of rain, sleet, snow.

NEMA 4

For indoor or outdoor use.

The NEMA 4 enclosure protects personnel from gaining easy access to hazardous parts. Also, it will protect the equipment inside the enclosure of falling dirt, windblown dust, rain, sleet, snow, and the formation of ice. It also has an ingress protection of splashing water, hose directed water.

NEMA 4X

For indoor or outdoor use.

The NEMA 4X enclosure protects personnel from gaining easy access to hazardous parts. Also, it will protect the equipment inside the enclosure of windblown dust, rain, sleet, snow, additional level of protection against corrosion, and the formation of ice. It also has an ingress protection of splashing water, hose directed water.

NEMA 12

For indoor use only.

The NEMA 12 enclosure (without knockouts) protects personnel against access to hazardous parts. Also, it will protect the equipment inside the enclosure of falling dirt, circulating dust, fibers. It also has an ingress protection of dripping and a light splashing of water.