Support for Model: TFLC9000E
Dyna Tri-Fuel Portable 9kw Generator
General Information | ||
Operators Manual | Parts List | |
Generator | ||
Troubleshooting Guide |
Dyna Tri-Fuel Portable 9kw Generator
General Information | ||
Operators Manual | Parts List | |
Generator | ||
Troubleshooting Guide |
Question
Jim –
what is T.H.D. of my tflc generator Thank you Jim
Upvote if this was helpful (0) Downvote if this was not helpful (0) Watch Unwatch Flag for removal
Question
Doug Fraser –
I have a Dyna TFLC9000E/N model, running on propane. My generator is about 22 years old. It is running low voltage, around 106V, but everything else seems normal. I have some mechanical/electrical abilities, can you suggest where to start looking? Troubleshooting guide does not appear to list this issue.
Upvote if this was helpful (0) Downvote if this was not helpful (0) Watch Unwatch Flag for removal
Dale Riebel –
Doug,
First check your frequency. If you are running between 60-62 hertz no load, then next I would check your capacitors. There are three of them. They should read 40uf capacitance + or – 5%. Please follow that troubleshooting guide and if you have questions please call our Service Department @ 507-357-6831.
Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal
Question
edward johnson –
model tflc9000e is this generator mass. state approved ?
Upvote if this was helpful (0) Downvote if this was not helpful (0) Watch Unwatch Flag for removal
Dale Riebel –
Edward, your model was made to sell in all 50 states in USA. Please consult your local authorities for your specific application.
Upvote if this was helpful (0) Downvote if this was not helpful (0) Flag for removal